Sanyo Air Conditioning Fault Codes Complete List
ADDRESSING & COMMUNICATION PROBLEMS
|
Code |
Description |
|
E01 |
Remote control detecting error from indoor
unit,Address not set/Auto address failed. Check interconnecting wir- |
|
ing etc. Re-address system. |
|
E02 |
Remote detecting error from indoor unit,
|
|
E03 |
Indoor unit detecting error from remote,
|
|
E04 |
Indoor seeing error from outdoor. Qty of i/d units
connected are less than qty set. Check; all i/d units are ON,
|
|
reset turn off all units wait 5min power up
|
|
E05 |
Indoor unit detecting error from outdoor unit, Error
in sending comms signal |
|
E06 |
Outdoor unit detecting error from indoor unit, Error
in receiving comms signal |
|
E07 |
Outdoor unit detecting error from indoor unit, Error
in sending comms signal |
|
E08 |
Incorrect setting indoor/controller, Indoor address
duplicated |
|
E09 |
Incorrect setting indoor/controller, Remote address
duplicated or IR wireless controller not disabled |
|
E10 |
Indoor unit detecting error from 'option' plug,
Error in sending comms signal |
|
E11 |
Indoor unit detecting error from 'option' plug,
Error in receiving comms signal |
|
E12 |
Auto addressing failed,Auto address connector CN100
shorted during auto addressing |
|
E13 |
Indoor unit failed to send signal to remote
controller |
|
E14 |
Setting Failure, Duplication of master indoor units
|
|
E15 |
Auto addressing failed, Number of indoor units
connected are less than number set |
|
E16 |
Auto addressing failed, Number of indoor units
connected are more than number set |
|
E17 |
Group control wiring error, Main indoor unit not
sending signal for sub indoor units |
|
E18 |
Group control wiring error, Main indoor unit not
receiving signal for sub indoor units |
|
E20 |
Auto addressing failed, No indoor units connected
|
|
E24 |
Auto addressing failed, Error on sub outdoor unit
|
|
E25 |
Auto addressing failed, Error on outdoor unit
address setting |
|
E26 |
Auto addressing failed, Quantity of main and sub
outdoor units do not correspond to the number set on main
|
|
outdoor unit P.C.B. |
|
E29 |
Auto addressing failed, Sub outdoor unit not
receiving comms for main outdoor unit |
|
E31 |
Between units, Comms failure with MDC, does E31
remain after power is re instated? If so replace PCB. & power
|
|
PCB |
Senior Faults
|
Code |
Description |
|
F01 |
Indoor Heat Exch inlet temp sensor failure (E1)
|
|
F02 |
Indoor Heat Exch freeze temp sensor failure (E2)
|
|
F03 |
Indoor Heat Exch outlet temp sensor failure (E3)
|
|
F04 |
Outdoor Discharge temp sensor failure (TD) or
(DISCH1) |
|
F05 |
Outdoor Discharge temp sensor failure (DISCH2)
|
|
F06 |
Outdoor Heat Exch temp sensor failure (C1) or (EXG1)
|
|
F07 |
Outdoor Heat Exch temp sensor failure (C2) or (EXL1)
|
|
F08 |
Outdoor Air temp sensor failure (TO) |
|
F10 |
Indoor inlet temp sensor failure |
|
F11 |
Indoor outlet temp sensor failure |
|
F12 |
Outdoor Intake sensor failure (TS) |
|
F13 |
GHP - Cooling water temperature sensor failure
|
|
F16 |
Outdoor High pressure sensor failure |
|
F17 |
GHP - Cooling water temperature sensor fault
|
|
F18 |
GHP - Exhaust gas temperature sensor fault
|
|
F20 |
GHP Clutch coil temperature fault |
|
F23 |
Outdoor Heat Exch temp sensor failure (EXG2)
|
|
F24 |
Outdoor Heat Exch temp sensor failure (EXL2)
|
|
F29 |
Indoor EEPROM error |
|
F30 |
Clock Function (RTC) fault |
|
F31 |
Outdoor EEPROM error |
Compressor Faults
|
Code |
Description |
|
H01 |
Compressor Fault, Over current (Comp1) |
|
H02 |
Compressor Fault, Locked rota current detected
(Comp1) |
|
H03 |
Compressor Fault, No current detected (Comp1)
|
|
H05 |
Compressor Fault, Discharge temp not detected
(Comp1) |
|
H06 |
Compressor Fault, Low Pressure trip |
|
H07 |
Compressor Fault, Low oil level |
|
H08 |
Compressor Fault, Oil sensor Fault (Comp1)
|
|
H11 |
Compressor Fault, Over current (Comp2) |
|
H12 |
Compressor Fault, Locked rota current detected
(Comp2) |
|
H13 |
Compressor Fault, No current detected (Comp2)
|
|
H15 |
Compressor Fault, Discharge temp not detected
(Comp2) |
|
H27 |
Compressor Fault, Oil sensor fault (Comp2)
|
|
H28 |
Compressor Fault. Oil sensor (connection failure)
|
|
H31 |
Compressor Fault. IPM trip (IMP current on
temperature) |
Incorrect Settings
|
Code |
Description |
|
L01 |
Setting Error, Indoor unit group setting error
|
|
L02 |
Setting Error, Indoor/outdoor unit type/model
miss-matched |
|
L03 |
Duplication of main indoor unit address in group
control |
|
L04 |
Duplication of outdoor unit system address
|
|
L05 |
2 or more controllers have been set as 'priority' in
one system - shown on controllers set as 'priority' |
|
L06 |
2 or more controllers have been set as 'priority' in
one system - shown on controllers not set as 'priority' |
|
L07 |
Group wiring connected on and indvidual indoor unit
|
|
L08 |
Indoor unit address/group not set |
|
L09 |
Indoor unit capacity code not set |
|
L10 |
Outdoor unit capacity code not set |
|
L11 |
Group contol wiring incorrect |
|
L13 |
Indoor unit type setting error, capacity
|
|
L15 |
Indoor unit paring fault |
|
L16 |
Water heat exch unit setting failure |
|
L17 |
Miss-match of outdoor unit with different
refrigerant |
|
L18 |
4-way valve failure |
|
L19 |
Water heat exch unit duplicated address |
|
L21 |
Gas type setup failure |
Indoor Faults
|
Code |
Description |
|
P01 |
Indoor unit fault, Fan motor thermal overload
|
|
P02 |
Outdoor unit fault, Compressor motor thermal
overload, over or under voltage |
|
P03 |
Outdoor unit fault, Compressor discharge temperature
too high (Comp1) over 111 degC. Low on ref gas, exp |
|
valve, pipework damage. |
|
P04 |
Outdoor unit fault, High pressure trip |
|
P05 |
Outdoor unit fault, Open phase on power supply.
Check power on each phase, inverter pcb, control pcb |
|
P09 |
Indoor unit fault, Ceiling panel incorrectly wired
|
|
P10 |
Indoor unit fault, Condensate float switch opened
|
|
P11 |
GHP - Water Heat exch low temp (frost protection)
fault |
|
P12 |
Indoor unit fault, Fan DC motor fault |
|
P14 |
Input from leak detector (If fitted) |
|
P15 |
Refrigerant loss, high discharge temp and EEV wide
open and low compressor current draw. |
|
P16 |
Outdoor unit fault, Open phase on compressor power
supply |
|
P17 |
Outdoor unit fault, Compressor discharge temperature
too high (Comp2) over 111 degC. Low on ref gas, exp |
|
valve, pipework damage. |
|
P18 |
Outdoor unit fault, By-pass valve failure
|
|
P19 |
Outdoor unit fault, 4 way valve failure, i/door temp
rises in cooling or fulls in heating. Check wiring, coil, pcb
output, |
|
valave operation. |
|
P20 |
Ref gas, high temp/pressure fault, heat exch temp
high C2, 55-60 degC, cooling over-load, sensor fault. |
|
P22 |
Outdoor unit fan motor fault, fan blade jammed,
check connections, does fan turn freely, motor resistance 30- |
|
40ohm on each pair, no fan fault, yes pcb fault.
|
|
P26 |
Outdoor unit fault, Compressor overcurrent - check
winding resistance, Inverter failure - check internal resistance
|
|
term HIC + & - to UVW 200-300Kohm or more
|
|
P29 |
Outdoor unit fault, Inverter circuit fault -
Motor-current Detection Circuit (MDC) fault, check comp windings,
sen- |
|
sors C1 & TS, if ok possible pcb failure.
|
|
P30 |
Indoor unit fault, System controller detected fault
on sub indoor unit |
|
P31 |
Simultaneous operation multi control fault, Group
controller fault |
|
|
|