In collaboration with Thermoscreens, Mitsubishi Electric air conditioning have developed a range of air curtains that are able to be connected to the Power Inverter heat pumps, as opposed to the more traditional direct electric method associated with air curtains. This reduces CO2 emissions/ running costs by up to 67% with a 2.5 year payback period against equivalent Electric system.

Key Product Features:

Product Data:

MODEL REFERENCE

PHV1000R DXE HO

PHV1500R DXE LO

PHV1500R DXE HO

PHV2000R DXE LO

PHV2000R DXE HO

DIMENSIONS (mm) (WxDxH)

1150x436x296

1650x436x296

1650x436x296

2240x436x296

2240x436x296

SUPPLY (50Hz)

415V*1

415V*1

415V*1

415V*2

415V*2

HEAT OUTPUT (kW)

100% / 50%

8.6 / 5.34

10.1 / 5.6

14.4 / 8.3

14.1 / 7.9

21.3 / 11.2

COP

100% / 50%

2.4 / 3.15

2.3 / 3.4

2.5 / 3.7

2.9 / 3.7

2.4 / 3.2

LOADING (amps)

9.2*1

12.7*1

12.7*1

15.7*2

15.7*2

VELOCITY (m/s)

9

9

9

9.5

9

AIR VOLUME (m3/h)

1400

2500

2600

3300

3130

WEIGHT (kg)

45

66

67

85

88

dB(A) @ 3m

100% / 50%

59 / 57

60 / 58

60 / 58

61 / 59

61 / 59

MAX. MOUNTING HEIGHT (m)

3.5

3.5

3.5

3.5

3.5

OUTDOOR UNIT MODEL

PUHZ-RP71VHA4

PUHZ-RP71VHA4

PUHZ-RP140VKA/YKA

PUHZ-RP100VKA/YKA

PUHZ-RP200YKA

Notes: *1 for units with electric heaters disabled, 240v power supply 1.8 amp load (1.3 amp load for PHV1000R DXE HO) *2 for units with electric heaters disabled, 240v power supply 2.7 amp load.

 

MODEL REFERENCE

PHV1000 DXE HO

PHV1500 DXE LO

PHV1500 DXE HO

PHV2000 DXE LO

PHV2000 DXE HO

DIMENSIONS (mm) (WxDxH)

1196x377x255

1746x377x255

1746x377x255

2296x377x255

2296x377x255

SUPPLY (50Hz)

415V*1

415V*1

415V*1

415V*2

415V*2

HEAT OUTPUT (kW)

100% / 50%

8.6 / 5.34

10.1 / 5.6

14.4 / 8.3

14.1 / 7.9

21.3 / 11.2

COP

100% / 50%

2.4 / 3.15

2.3 / 3.4

2.5 / 3.7

2.9 / 3.7

2.4 / 3.2

LOADING (amps)

9.2*1

12.7*1

12.7*1

15.7*2

15.7*2

VELOCITY (m/s)

9

9

9

9.5

9

AIR VOLUME (m3/h)

1400

2500

2600

3300

3130

WEIGHT (kg)

39

59

60

78

80

dB(A) @ 3m

100% / 50%

59 / 57

60 / 58

60 / 58

61 / 59

61 / 59

MAX. MOUNTING HEIGHT (m)

3.75

3.75

3.75

3.75

3.75

OUTDOOR UNIT MODEL

PUHZ-RP71VHA4

PUHZ-RP71VHA4

PUHZ-RP140VKA/YKA

PUHZ-RP100VKA/YKA

PUHZ-RP200YKA

Notes: *1 for units with electric heaters disabled, 240v power supply 1.8 amp load (1.3 amp load for PHV1000 DXE HO) *2 for units with electric heaters disabled, 240v power supply 2.7 amp load.

 

 

MODEL REFERENCE

PUHZ-RP71VHA4

PUHZ-RP100VKA/YKA

PUHZ-RP140VKA/YKA

PUHZ-RP200YKA

DIMENSIONS (mm) (WxDxH)

950x330+30x943

1050x330+30x1338

1050x330+30x1338

1050x330+30x1338

SUPPLY (50Hz)

230V

230V / 415V

230V / 415V

415V

MAX. CURRENT (A)

19

26.5 / 8

28 / 11

19

FUSE SIZE HRC (BS88)

20

32 / 10

32 / 16

20

MAX. PIPE RUN

Length (m)

50

50

50

100

Height (m)

30

30

30

30

PIPE SIZES

Gas mm(in)

15.88 (5/8)

15.88 (5/8)

15.88 (5/8)

28.58 (1 1/8)

Liquid mm(in)

9.52 (3/8)

9.52 (3/8)

9.52 (3/8)

9.52 (3/8)

INTERCONNECTING CABLE

2 core

2 core

2 core

2 core