| 
               Diagnosis
              
               
             | 
            
               Abnormality /
              
               
             | 
            
               Diagnosis Method
              
               
             | 
            
               Diagnosis Checkpoint
              
               
             | 
          
          
            | 
               Display
              
               
             | 
            
               Protection Control
              
               
             | 
              | 
              | 
          
          
            | 
               H11
              
               
             | 
            
               Indoor/Outdoor
              
               
             | 
            
               This trouble display appears when indoor/outdoor unit communication
              fails to be established after 30 or more
              
               
             | 
            
               Measure the voltages of the indoor/outdoor unit communication cables,
              and check whether the voltage is being
              
               
             | 
          
          
            |   | 
            
               abnormal
              
               
             | 
            
               seconds.
              
               
             | 
            
               supplied properly to the outdoor unit or whether it is being returned
              from the outdoor unit to the indoor units.
              
               
             | 
          
          
            |   | 
            
               communication
              
               
             | 
              | 
              | 
          
          
            | 
               H12
              
               
             | 
            
               Indoor unit capacity
              
               
             | 
            
               This trouble display appears when wrong in the total connection
              capacity and wrong connection in each capacity.
              
               
             | 
            
               Check the total capacity of the units connected and check that the
              models are compatible for connection.
              
               
             | 
          
          
            |   | 
            
               unmatched
              
               
             | 
            
               The trouble is determined within 2 minutes after the power is turned
              on.
              
               
             | 
              | 
          
          
            | 
               H14
              
               
             | 
            
               Intake air temp.
              
               
             | 
            
               This trouble display appears when the intake air temperature has
              exceeded above 46ºC continuously for 2 minutes
              
               
             | 
            
               This trouble display appears when a temperature which is impossibly
              high or low from a normal standpoint has
              
               
             | 
          
          
            |   | 
            
               sensor
              
               
             | 
            
               or dropped below -54ºC continuously for 5 seconds during operation.
              
               
             | 
            
               been detected. Check the sensor, and if open-circuiting (0L or ∞)
              or short-circuit is not found, defective contact of
              
               
             | 
          
          
            |   | 
              | 
              | 
            
               the connector is to blame.
              
               
             | 
          
          
            | 
               H15
              
               
             | 
            
               Outdoor compressor
              
               
             | 
            
               —
              
               
             | 
            
               Check the sensor, and if open-circuit (more than 500 k) or
              (short-circuit) (less than 6.5 k) is not found, defective
              
               
             | 
          
          
            |   | 
            
               temperature sensor
              
               
             | 
              | 
            
               contact of the connector is to blame.
              
               
             | 
          
          
            |   | 
            
               abnormality
              
               
             | 
              | 
              | 
          
          
            | 
               H16
              
               
             | 
            
               Outdoor Current
              
               
             | 
            
               CU-2E: When a value of under 1.5A has been detected for the total
              current during operation beyond the set
              
               
             | 
            
               1. Check the refrigerant cycle: Gas may be leaking (the amount of
              refrigerant is extremely low).
              
               
             | 
          
          
            |   | 
            
               Transformer
              
               
             | 
            
               capacity, the compressor operates with its operating frequency
              controlled to a maximum of 38Hz for 3 minutes,
              
               
             | 
            
               2. Check the control PCB: Check for a broken wire (open circuit) in the
              current transformer. (If an open circuit is
              
               
             | 
          
          
            |   | 
              | 
            
               and if it continues to operate at a total current of under 1.5A for
              another 3 minutes, its operation stops.
              
               
             | 
            
               found, replace the control PCB) In the case of a scroll compressor (DC
              motor), H16 is detected only when the
              
               
             | 
          
          
            |   | 
              | 
            
               CU-3E/4E: When the total current has dropped below the set current
              level continuously for 20 seconds during
              
               
             | 
            
               regular compressor is operating.
              
               
             | 
          
          
            |   | 
              | 
            
               operation beyond the set capacity, operation is stopped. Three minutes
              later, operation is started up again, and
              
               
             | 
              | 
          
          
            |   | 
              | 
            
               when the trouble occurs on 4 successive occasions, the trouble display
              appears (the timer lamp blinks).
              
               
             | 
              | 
          
          
            | 
               H19
              
               
             | 
            
               Indoor fan motor
              
               
             | 
            
               · High-voltage PWM: When a state in which the fan motor speed is not
              synchronized with the control signal has been
              
               
             | 
            
               1. Check the nature of the fan lockup trouble.
              
               
             | 
          
          
            |   | 
            
               mechanism lock
              
               
             | 
            
               detected on 7 successive occasions.
              
               
             | 
            
               2. Check for disconnections of the fan motor connectors and for defects
              in contact, in the fan motor and in the
              
               
             | 
          
          
            |   | 
              | 
            
               · Low-voltage PAM: When the fan lock detection signal has been
              detected on 7 successive occasions or it has been
              
               
             | 
            
               control PCB.
              
               
             | 
          
          
            |   | 
              | 
            
               detected continuously for 25 seconds or when a state in which the fan
              motor speed is not synchronized with the control
              
               
             | 
              | 
          
          
            |   | 
              | 
            
               signal has been detected on 7 successive occasions: The trouble display
              appears (the timer lamp blinks).
              
               
             | 
              | 
          
          
            | 
               H23
              
               
             | 
            
               Indoor heat exchanger
              
               
             | 
            
               This trouble display appears when a temperature of under approximately
              -40ºC or above approximately 80ºC has
              
               
             | 
            
               This trouble display appears when a temperature which is impossibly
              high or low from a normal standpoint has
              
               
             | 
          
          
            |   | 
            
               temp. sensor
              
               
             | 
            
               been detected by the heat exchanger temperature sensor continuously for
              5 seconds. (This trouble is not detected
              
               
             | 
            
               been detected. Check the sensor, and if (open-circuit) (0L or ∞)
              or short-circuit is not found, defective contact of
              
               
             | 
          
          
            |   | 
              | 
            
               during de-icing.)
              
               
             | 
            
               the connector or a defective control PCB is to blame.
              
               
             | 
          
          
            | 
               H26
              
               
             | 
            
               Ionizer Abnormality
              
               
             | 
            
               —
              
               
             | 
            
               1. Measure the voltages of the indoor unit communication cables, and
              check whether the voltage is being supplied
              
               
             | 
          
          
            |   | 
              | 
              | 
            
               properly. 2. Check the ionizer needle and grounding plate is dust free.
              
               
             | 
          
          
            | 
               H27
              
               
             | 
            
               Outdoor air temp.
              
               
             | 
            
               This trouble display appears when a temperature of under approximately
              -40ºC or above approximately 150ºC has
              
               
             | 
            
               This trouble display appears when a temperature which is impossibly
              high or low from a normal standpoint has
              
               
             | 
          
          
            |   | 
            
               sensor
              
               
             | 
            
               been detected by the outside air temperature sensor for 2 to 5 seconds.
              (This trouble is not detected during
              
               
             | 
            
               been detected. Check the sensor, and if open-circuiting (0L or ∞)
              or short-circuit isnot found, defective contact of
              
               
             | 
          
          
            |   | 
              | 
            
               de-icing.)
              
               
             | 
            
               the connector or a defective control PCB is to blame.
              
               
             | 
          
          
            | 
               H28
              
               
             | 
            
               Outdoor heat
              
               
             | 
            
               This trouble display appears when a temperature of under approximately
              -60ºC or above approximately 110ºC has
              
               
             | 
            
               This trouble display appears when a temperature which is impossibly
              high or low from a normal standpoint has
              
               
             | 
          
          
            |   | 
            
               exchanger temp.
              
               
             | 
            
               been detected by the heat exchanger temperature sensor for 2 to 5
              seconds. (This trouble is not detected during
              
               
             | 
            
               been detected. Check the sensor, and if open-circuiting (0L or ∞)
              or short-circuit is not found, defective contact of
              
               
             | 
          
          
            |   | 
            
               sensor 1
              
               
             | 
            
               de-icing.)
              
               
             | 
            
               the connector or a defective control PCB is to blame.
              
               
             | 
          
          
            | 
               H30
              
               
             | 
            
               Outdoor discharge
              
               
             | 
            
               CU-2E: This trouble display appears when a temperature of under
              approximately -16ºC or above approximately
              
               
             | 
            
               This trouble display appears when a temperature which is impossibly
              high or low from a normal standpoint has
              
               
             | 
          
          
            |   | 
            
               pipe temp. sensor
              
               
             | 
            
               200ºC has been detected by the outlet temperature sensor for 2 to 5
              seconds.
              
               
             | 
            
               been detected. Check the sensor, and if open-circuiting (0L or ∞)
              or short-circuit is not found, defective contact of
              
               
             | 
          
          
            |   | 
              | 
            
               CU-3E/4E: Disconnected discharge sensor · When the condensation
              temperature is higher than the discharge
              
               
             | 
            
               the connector or a defective control PCB is to blame.
              
               
             | 
          
          
            |   | 
              | 
            
               temperature + (plus) 6ºC, a sensor disconnection is detected,
              operation stops, and the trouble display appears
              
               
             | 
              | 
          
          
            |   | 
              | 
            
               (the timer lamp blinks).
              
               
             | 
              | 
          
          
            | 
               H32
              
               
             | 
            
               Outdoor heat exchanger
              
               
             | 
            
               This trouble display appears when a temperature of under approximately
              -60ºC or over approximately 110ºC has
              
               
             | 
            
               This trouble display appears when a temperature which is impossibly
              high or low from a normal standpoint has
              
               
             | 
          
          
            |   | 
            
               temp. sensor 2
              
               
             | 
            
               been detected continuously for 2 to 5 seconds by the outlet temperature
              sensor of the heat exchanger.
              
               
             | 
            
               been detected. Check the sensor, and if open-circuiting (0L or ∞)
              or short-circuit is not found, defective contact of
              
               
             | 
          
          
            |   | 
            
               (discharge pipe temp.)
              
               
             | 
              | 
            
               the connector or a defective control PCB is to blame.
              
               
             | 
          
          
            | 
               H33
              
               
             | 
            
               Indoor / Outdoor
              
               
             | 
            
               Indoor / Outdoor different model junction, 100V charge into 200V
              outdoor unit.
              
               
             | 
            
               Check whether the voltage is being supplied properly to the outdoor
              unit or whether it is being returned from the
              
               
             | 
          
          
            |   | 
            
               wrong connection
              
               
             | 
              | 
            
               outdoor unit to the indoor units.
              
               
             | 
          
          
            | 
               H34
              
               
             | 
            
               Outdoor heat sink
              
               
             | 
            
               This trouble display appears when a temperature of under -43ºC or
              above 80ºC has been detected by the outdoor
              
               
             | 
            
               This trouble display appears when a temperature which is impossibly
              high or low from a normal standpoint has
              
               
             | 
          
          
            |   | 
            
               temp. sensor
              
               
             | 
            
               unit radiator fin sensor continuously for 2 seconds.
              
               
             | 
            
               been detected. Check the sensor, and if open-circuiting (0L or ∞)
              or short-circuit is not found, defective contact of
              
               
             | 
          
          
            |   | 
              | 
              | 
            
               the connector or a defective control PCB is to blame.
              
               
             | 
          
          
            | 
               H36
              
               
             | 
            
               Abnormal gas pipe
              
               
             | 
            
               This trouble display appears when a temperature of under approximately
              -45ºC or above approximately 149ºC has
              
               
             | 
            
               This trouble display appears when a temperature which is impossibly
              high or low from a normal standpoint has
              
               
             | 
          
          
            |   | 
            
               temp. sensor
              
               
             | 
            
               been detected by the outdoor unit gas side pipe temperature sensor
              continuously for 2 to 5 seconds.
              
               
             | 
            
               been detected. Check the sensor, and if open-circuiting (0L or ∞)
              or short-circuit is not found, defective contact of
              
               
             | 
          
          
            |   | 
              | 
              | 
            
               the connector or a defective control PCB is to blame.
              
               
             | 
          
          
            | 
               H37
              
               
             | 
            
               Outdoor liquid pipe
              
               
             | 
            
               This trouble display appears when a temperature of under -45ºC or
              above 149ºC has been detected by the outdoor
              
               
             | 
            
               This trouble display appears when a temperature which is impossibly
              high or low from a normal standpoint has
              
               
             | 
          
          
            |   | 
            
               temp. sensor
              
               
             | 
            
               unit liquid side pipe temperature sensor continuously for 2 seconds.
              
               
             | 
            
               been detected. Check the sensor, and if open-circuiting (0L or ∞)
              or short-circuit is not found, defective contact of
              
               
             | 
          
          
            |   | 
              | 
              | 
            
               the connector or a defective control PCB is to blame.
              
               
             | 
          
          
            | 
               H38
              
               
             | 
            
               Indoor / Outdoor
              
               
             | 
            
               —
              
               
             | 
            
               —
              
               
             | 
          
          
            |   | 
            
               mismatch (brand code)
              
               
             | 
              | 
              | 
          
          
            | 
               H39
              
               
             | 
            
               Abnormal indoor
              
               
             | 
            
               This display appears in rooms other than one in which indoor freezing
              trouble has occurred when the pipes have
              
               
             | 
            
               —
              
               
             | 
          
          
            |   | 
            
               operating unit or
              
               
             | 
            
               been connected incorrectly, when an outdoor expansion valve is
              defective or when an expansion valve connector
              
               
             | 
              | 
          
          
            |   | 
            
               standBy units
              
               
             | 
            
               has become disconnected.
              
               
             | 
              | 
          
          
            | 
               H41
              
               
             | 
            
               Abnormal wiring or
              
               
             | 
            
               CU-2E only This display appears when this kind of trouble is detected 3
              minutes after a forced cooling operation
              
               
             | 
            
               —
              
               
             | 
          
          
            |   | 
            
               piping connection
              
               
             | 
            
               was conducted for one room during the initial operation after the power
              was turned on. It appears when:
              
               
             | 
              | 
          
          
            |   | 
              | 
            
               · The indoor unit pipe temperature in a room without the capacity
              supply available at an outside air temperature
              
               
             | 
              | 
          
          
            |   | 
              | 
            
               above 5ºC has dropped by more than 20ºC to 5ºC or lower 3 minutes
              after the compressor started up. · The
              
               
             | 
              | 
          
          
            |   | 
              | 
            
               outdoor unit gas pipe temperature in a room without the capacity supply
              available has dropped by more than 5ºC
              
               
             | 
              | 
          
          
            |   | 
              | 
            
               to 5ºC or lower 3 minutes after the compressor started up.
              
               
             | 
              | 
          
          
            | 
               H50
              
               
             | 
            
               Ventilation failure
              
               
             | 
            
               This display appears when ventilation motor is lock.
              
               
             | 
            
               1. Check the voltage drop at pin 1 & 2 of CNVENT to have 14Vdc. 2.
              Check the ventilation hose condition from
              
               
             | 
          
          
            |   | 
              | 
              | 
            
               ventilation opening until tip cover. 3. Check air fl ow from tip cover
              by hand.
              
               
             |