| 
         
 
 Call: +44(0)1234 841221 E-mail: [email protected] 
 Sanyo SAP commercial and residential air conditioning systems. Trouble shooting, installation, controller information and service data. 
 
 
 
 
         
         
         Room
        Temperature Control of the air conditioning system Cooling Room
        temperature control is obtained by cycling the compressor ON and OFF
        under control of the room temperature sensor in the remote control unit. l
        The
        room temperature (and other information) is transmitted every 5 minutes
        by the remote control unit to the controller in the indoor unit. l Once
        the compressor starts, it keeps running for 5 minutes. l Once
        the compressor stops, it will not start running again for 3 minutes. l Thermo
        ON : When room temperature rises 1°C above the set temperature T°C. Compressor
        ή ON l Thermo.
        OFF : When the room temperature decreases below the set temperature
        T°C. Compressor
        ή OFF   n Heating  Room
        temperature control is obtained by cycling the compressor ON and OFF
        under control of the room temperature sensor in the remote control unit.
         The
        room temperature (and other information) is transmitted every 5 minutes
        by the remote control unit to the controller in the indoor unit.  Once
        the compressor starts, it keeps running for 5 minutes.  Once
        the compressor stops, it will not start running again for 5 minutes.
        Thermo ON : When room temperature decreases below 1°C below the set
        temperature T°C. Compressor
        ή ON  Thermo.
        OFF : When the room temperature rises 1°C above the set temperature
        T°C. Compressor
        ή OFF The
        temperature described in this page and previous page gives you an
        example with remote control operation. In case of a body sensor
        operation, operation temperature differ somewhat.   Dry
        Operation (Dehumidification) of the air conditioning system Dry
        operation uses the ability of the cooling cycle to remove moisture from
        the air, but by running at low level to dehumidify without greatly
        reducing the room temperature. The air conditioner repeats the cycle of
        turning ON and OFF automatically as shown in the chart below according
        to the room temperature. Automatic
        Switching between Cooling and Heating of the air conditioning system When
        AUTO mode is selected, the microprocessor calculates the difference
        between the set temperature and the room temperature, and automatically
        switches to COOLING or HEATING mode to maintain the desired temperature. Room
        temp. ³
        Set
        temp. ή COOL Room
        temp. < Set temp. ή HEAT This
        means that if the room temperature is higher than or equal to the
        set temperature, COOLING operation begins. If the room
        temperature is lower than the set temperature, HEATING operation
        begins. Example of operation in the AUTO mode with the set room
        temperature at 23 °C.
        The air conditioner changes the operation mode (from cool to heat or
        vice versa) TROUBLESHOOTING
        the air conditioning system Check
        power supply wiring Check
        that power supply wires are correctly connected to terminals L and
        N on the terminal plate in the indoor unit. 9-1-2.
        Check inter-unit wiring. Check
        that inter-unit wiring is correctly connected between indoor unit and
        outdoor unit. 9-1-3.
        Check power supply. Check
        that voltage is in specified range (±10% of the rating).
         Check
        that power is being supplied. 9-1-4.
        Check lead wires and connectors in indoor and outdoor units. Check
        that coating of lead wires is not damaged.  Check that lead wires and connectors
        are firmly connected. Check that wiring is correct. 2.
        Air conditioner does not operate. 9-2-1.
        Circuit breaker trips (or fuse blows). A. When the circuit breaker is set to ON, it is tripped soon.
        (Resetting is not possible.) There
        is a possibility of ground fault. Check insulation resistance. If
        resistance value is 2M½
        or
        less, insulation is defective 
     
 
                                   
   
   11.
        CHECKING ELECTRICAL Components 11-1.
        Measurement of Insulation Resistance  The
        insulation is in good condition if the resistance exceeds 1M½. 11-1-1.
        Power supply cord Clamp the grounding wire of power cord with the lead clip of the
        insulation resistance tester and measure the resistance by placing a
        probe on either of the two power wires. Then also measure the resistance
        between the grounding and other power terminals. (Fig. 1) 11-1-2.
        Indoor unit Clamp an aluminum plate fin or copper tube with the lead clip of the
        insulation resistance tester and measure the resistance by placing a
        probe on each terminal screw where power supply lines are connected on
        the terminal plate. 11-1-3.
        Outdoor unit Clamp an aluminum plate fin or copper tube with the lead clip of the
        insulation resistance tester and measure the resistance by placing a
        probe on each terminal screw on the terminal plate. Note that the ground
        line terminal should be skipped for the check. 11-1-4.
        Measurement of insulation resistance
        for electrical parts Disconnect the lead wires of the desired electric part from terminal
        plate, capacitor, etc. Similarly disconnect the connector. Then measure
        the insulation resistance. 12.
        REFRIGERANT R410A: SPECIAL PRECAUTIONS WHEN SERVICING UNIT 12-1.
        Characteristics of New Refrigerant R410A 12-1-1.
        What is New Refrigerant R410A? R410A is a new refrigerant that contains two types of
        pseudo-non-azeotropic refrigerant mixture. Its refrigeration capacity and energy efficiency are about the same
        level as the conventional refrigerant, R22. 12-1-2.
        Components (mixing proportions) HFC32 (50%) / HFC125 (50%) 12-1-3.
        Characteristics Less
        toxic, more chemically stable refrigerant The composition of refrigerant
        R410A changes whether it is in a gaseous phase or liquid phase. Thus,
        when there is a refrigerant leak the basic performance of the air
        conditioner may be degraded because of a change in composition of the
        remaining refrigerant. Therefore, do not add new refrigerant. Instead,
        recover the remaining refrigerant with the refrigerant recovery unit.
        Then, after evacuation, totally recharge the specified amount of
        refrigerant with the new refrigerant at its normal mixed composition
        state (in liquid phase). l
        When
        refrigerant R410A is used, the composition will differ depending on
        whether it is in gaseous or liquid phase, and the basic performance of
        the air conditioner will be degraded if it is charged while the
        refrigerant is in gaseous state. Thus, always charge the refrigerant
        while it is in liquid phase. 12-2.
        Checklist Before Servicing Use a clutch-type flare tool for R410A or the conventional flare
        tool. Note that sizes of the resultant flares differ between these two
        tools. Where a conventional flare tool is used, make sure to observe A
        Specification (amount of extrusion) by using the flare spacer.  Tubing
        precautions Refrigerant
        R410A is more easily affected by dust or moisture compared with R22,
        thus be sure to temporarily cover the ends of the tubing with caps or
        tape prior to installation. Never
        use 0.7mm-thick copper tubing or tubing which is less than 0.8mm in
        thickness, since air conditioners with R410A are subject to higher
        pressure than those using R22 and R407C. No
        addition of compressor oil for R410A No
        additional charge of compressor oil is permitted.  No
        use of refrigerant other than R410A Never
        use a refrigerant other than R410A.  If
        refrigerant R410A is exposed to fire Through
        welding, etc., toxic gas may be released when R410A refrigerant is
        exposed to fire. Therefore, be sure to provide ample ventilation during
        installation work. Caution in case of R410A leak Check for possible leak points with the special leak detector for
        R410A. If a leak occurs inside the room, immediately provide thorough
        ventilation. 12-5-1.
        Procedure for replacing compressor (1) Recovering refrigerant Any
        remaining refrigerant inside the unit should not be released to the
        atmosphere, but recovered using the refrigerant recovery unit for R410A.
        Do not reuse the recovered refrigerant, since it will contain
        impurities. (2) Replacing Compressor l
        Soon
        after removing seals of both discharge and suction tubes of the new
        compressor, replace it quickly. (3) Checking for sealing Use
        nitrogen gas for the pressurized gas, and never use a refrigerant other
        than R410A. Also do not use oxygen or any flammable gas. (4) Evacuation Use
        a solenoid valve-installed vacuum pump so that even if power is cut off in the middle of evacuation of air
        due to a power interruption, the valve will prevent the pump oil from
        flowing back.
         The
        equipment may be damaged if moisture remains in the tubing, thus carry
        out the evacuation thoroughly.
         When
        using a vacuum pump with exhaust air volume more than 25L/min. and
        ultimate vacuum pressure rate of 0.05Torr:   
 (5) Recharging Be
        sure to charge the specified amount of refrigerant in liquid state using
        the service port of the wide tube service valve. The proper amount is
        listed on the unit's nameplate. When the entire amount cannot be charged
        all at once, charge gradually while operating the unit in Cooling
        Operation. When charging with a refrigerant cylinder, use an electronic
        scale for charging refrigerant. In this case, if the volume of
        refrigerant in the cylinder becomes less than 20% of the fully-charged
        amount, the composition of the refrigerant starts to change. Thus, do
        not use the refrigerant if the amount in the charging cylinder is less
        than 20%. Also, charge the minimum necessary amount to the charging
        cylinder before using it to charge the air conditioning unit. Example: In case of charging refrigerant to a unit requiring 0.76Kg using a
        capacity of a 10Kg cylinder, the minimum necessary amount for the
        cylinder is: 0.76 + 10 ΄
        0.20 = 2.76Kg For the remaining refrigerant, refer to the instructions of the
        refrigerant manufacturer. l
        If
        using a charging cylinder, transfer the specified amount of liquid
        refrigerant from the refrigerant cylinder to the charging cylinder.
        Prepare an evacuated charging cylinder beforehand. Do not use the
        refrigerant if the amount in the charging cylinder is less than 20%. CAUTION Never charge a large amount of liquid refrigerant
        at once to the unit. This may cause damage to the compressor.
        CAUTION  To
        prevent the composition of R410A from changing, never bleed the
        refrigerant gas into the atmosphere while transferring the refrigerant.   12-7.
        Charging Additional Refrigerant 12-7-1.
        When Tubes are Extended l Observe
        the proper amount of refrigerant as stated in this service manual or the
        installation manual that came with the indoor unit. Charge additional
        refrigerant in liquid state only. 12-8.
        Retro-Fitting Existing Systems 12-8-1.
        Use of Existing Units l Never
        use new refrigerant R410A for existing units which use R22.This
        will cause the air conditioner to operate improperly and may result in a
        hazardous condition. 12-8-2.
        Use of Existing Tubing If
        replacing an older unit that used refrigerant R22 with a R410A unit, do
        not use its existing tubing. Instead, completely new tubing must be
        used. CAUTION
        Never
        charge additional refrigerant if refrigerant is leaking from the unit.
        Follow instructions given in 12-6. In Case Refrigerant is Leaking
        and completely carry out repairs. Only then should you recharge the
        refrigerant.   Links: Sanyo
        Air Conditioning SPW error codes Contact Us:Spare
        Parts: +44 (0)1234 841221 
 
 
 
 
  | 
    |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| 
         home | sitemap | JetHeat Heaters | JetFlow Portable Fans And Extractors | Space Heaters | Privacy 
  | 
      
         Orion Air conditioning and refrigeration ltd. All rights reserved Created@2005 Last updated - 17/05/2020  |